3-14 Receiving & Installation MN722
Figure 3-2 Configuring the Control Transformer for 380 - 400 VAC Installation
Contactor Transformer
Only size E and F controls require a change of the contactor transformer tap.
See Figure 3-3. Use the taps (H1 to H5) that are correct for the input voltage.
Figure 3-3 Contactor Transformer Tap Change (380 -400VAC Input)
H2
H3
H4
H5
380VAC
440VAC
550VAC
600VAC
H1
Voltage Taps
380
440-460
550
600
H1 H2
H1 H3
H1 H4
H1 H5
Frequency
50 / 60
Hz
Size G+and H control procedure: (Refer to Figure 3-4.)
Control Transformer
1. Be sure drive operation is terminated and control is disabled.
2. Remove all power sources from the control. If power has been applied, wait at
least 5 minutes for bus capacitors to discharge.
3. Remove or open the front cover. Locate the control transformer fuse block
(see Figure 3-1).
4. Remove the wires from the two right side terminals (460VAC connection).
5. Place the wires on the center terminals as shown (380VAC connection).
6. Install or close the front cover.
Figure 3-4 Configuring the Control Transformer Fuse Block for 380 - 400 VAC Installation
460VAC
Connection
380-400VAC
Connection
For Fuse Block, location
refer to Figure 3-1.